Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM04924
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Clarify occupanct load appears to be an occupant load of 5942 sf/5 = 848 vs 295 noted on Dwg #CI, ref IBC Chapter 10, Table 1003.2.2.2. 2. Clarify how one-hour fire-rated type of construction is maintained: 1. Provide details and listings on drawings for four new door openings at existing one-hour fire-rated exit corridors at each side of platform. 2. Provide details and listings on drawings for roof-ceiling assembly. 3. 20-minute door assembly ; doors, door frames and closers at four new openings at one-hour fire-rated corridors. per IBC Chapter 5, 6, 7 & 10. 3. Provide and detail handrails on each side of four stairs, per IBC Chapter 10, 11 and ANSI A117.1-1998 ed, with extensions. 4. Clarify accessibility, show where 20% of project valuation is spent on accessibility per IBC Chapter 11 & 34 and ANSI A117.1-1998 ed . Provide estimate on the drawings. 5. Show by specification interior finishes comply with IBC Chapter 8. 6. Note fire blocking on floor framing at platform per IBC Sec 716.2.7. 7. Indicate location of existing exit lighting, required per IBC Chapter 10, to be maintained. 8. Provide accessibility to platform per IBC Chapter 11 and ANSI A117.1-1998 ed , ref IBC Sec 1101 & 1102. 9. Show location of wheelchair spaces per IBC Chapter 11,34 and ANSI A117.1-1998 ed. 10. Provide structural calculations and details for new door openings ( 4 ) at corridors. Should you have questions regarding these comments please call Douglas G Laakso, Structural Plans Examiner at (520) 791-5550 x1111. |
| 11/03/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/03/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 11/03/2003 | JIM EGAN | FIRE | REVIEW | Denied | 1. Include occupant loads for "accordian partitioned" areas in occupant looad calculations. |
| 11/03/2003 | JIM EGAN | FIRE | REVIEW | Denied | Include occupant loads for "accordian partitioned" areas in occupant load calculations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 11/03/2003 | LISA LESNY | REJECT SHELF | Completed |