Permit Number: T03CM04916
Parcel: 11804188A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM04916
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2003 EROSE1 WWM REVIEW Needs Review
11/04/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 1
1. Please provide the item number of the dwelling unit separation wall from IBC Table 719.1(2) or the listing number from an approved testing agency. Ref. R321. Provide a detail of this wall.

2. Specify penetrations of the fire resistive wall to be fire resistance rated. Ref. R321.1.

STRUCTURAL COMMENTS
Sheet 2
1. Please specify the steel reinforcement for the post footing.

PLUMBING COMMENTS
Sheet 3
1. Please note 1994 UPC as amended by the City of Tucson as the governing plumbing code.

Sheet 7
1. Revise section VII plumbing notes to reference the UPC. The City of Tucson local amendments eliminate Chapters 25 through 32 of the IRC and portions of Chapter 24.

MECHANICAL COMMENTS
Sheet 4
1. Please specify material, size and path for condensate disposal. Ref. M1411.

ELECTRICAL COMMENTS
Sheet 4
1. Distribute convenience receptacles so that no point along the wall is more than 6 feet from an outlet. Ref. E3801.2.

2. Provide a receptacle for the hallway which is greater than 10 feet in length. Ref. E3801.10.

3. Please show circuits 14 and 16 as spares in the panel schedule.

ENERGY COMMENTS
General
1. Please provide the SEER rating for the mechanical equipment.
11/04/2003 EROSE1 WATER REVIEW Needs Review
11/04/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2003 ELAINE ROSE OUT TO CUSTOMER Completed