Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/10/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
10/10/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
10/29/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/29/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/29/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/30/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
11/03/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM04896 DENIED 10/30/03 1. Regarding the above-ceiling receptacles, per NEC 400-8, it is not permitted to use flexible cords where concealed behind suspended ceilings. Some modification would need to be taken to comply with 400-7, Used Permitted. Suggest one of the following: A: If the equipment being plugged into the above ceiling receptacles does not have a cord and plugs in directly, such as a low-voltage transformer, change the duplex to simplex receptacle. B: If the equipment has a cord, suggest a J-box for the receptacle and flexible conduit for the cord. Linda Buczynski 520.791.5550 x1106 |
11/13/2003 | MELISSA POULIN | WWM | REVIEW | Passed | |
11/13/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |