Permit Number: T03CM04896
Parcel: 11004345C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM04896
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
10/10/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
10/29/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/29/2003 ROBERT SHERRY WATER REVIEW Approved
10/29/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/30/2003 JIM EGAN FIRE REVIEW Approved
11/03/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM04896 DENIED 10/30/03
1. Regarding the above-ceiling receptacles, per NEC 400-8, it is not permitted to use flexible cords where concealed behind suspended ceilings. Some modification would need to be taken to comply with 400-7, Used Permitted. Suggest one of the following:
A: If the equipment being plugged into the above ceiling receptacles does not have a cord and plugs in directly, such as a low-voltage transformer, change the duplex to simplex receptacle.
B: If the equipment has a cord, suggest a J-box for the receptacle and flexible conduit for the cord.

Linda Buczynski
520.791.5550 x1106
11/13/2003 MELISSA POULIN WWM REVIEW Passed
11/13/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved