Permit Number: T03CM04891
Parcel: 11515114A

Address:
545 W PLATA ST

Review Status: Completed

Review Details: SITE

Permit Number - T03CM04891
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2003 JOE LINVILLE LANDSCAPE REVIEW Approved
10/20/2003 JOE LINVILLE NPPO REVIEW Approved
10/20/2003 ANY ENGINEERING REVIEW Denied To: Anthony Capps
Architect
Tucson, Arizona 85705

SUBJECT: 545 W. Plata Street
Site plan T03CM04891 (First Review)
T14S, R13E, Section 02

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies with resubmittal.
2. Rename the Paving and Grading plan to Site Paving and Grading plan.
3. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
4. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. Include extension lines on all dimensions.
5. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
6. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. It appears the refuse container is in an acceptable location, however please obtain permission from John Clark, dept. of Solid Waste at 791-5543.
7. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
8. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
9. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
10. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
11. No extruded curb is allowed in the Public Right-of-Way.
12. A new wheel chair ramp will be required. The exist. ramp is inadequate.
13. All sidewalks must be separated by a physical means per D.S. 2-08.4.1.

Drainage Statement:
1. A Drainage Statement is a brief description of conditions applicable for parcels not affected by 100-year flows of 100 cfs, of more per S.M.D.D.F.M., chap. II, 2.1.2, is required.
2. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.3.2.
3. Show the project address on the cover of the Drainage Statement.
10/20/2003 ANY SANITATION REVIEW Denied See engineering folder.
10/21/2003 JIM EGAN FIRE REVIEW Approved
10/22/2003 DAN CASTRO HANDICAP-SITE REVIEW Approved
10/22/2003 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2003 TAMI ACHONG OUT TO CUSTOMER Completed