Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Z_DO NOT USE T03CM04885 101003
1. Provide panel and circuit number for sump pump.
2. Show location of panel powering sump pump.
3. Show load calculations on panel powerinf sump pump.
4. Provide ground fault and short circuit protection for sump pump.
10/10/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/10/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show that the removal of the service sink will not effect the required minimum fixtures for the building. Reference section 2900, IBC 2000.
11/04/2003 MVALDEZ1 ZONING REVIEW Needs Review
11/04/2003 MVALDEZ1 WWM REVIEW Needs Review
11/04/2003 MVALDEZ1 BUILDING-COMMERCIAL REVIEW Needs Review
11/04/2003 MVALDEZ1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2003 MONICA VALDEZ OUT TO CUSTOMER Completed