Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM04884
Parcel: 133231610

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM04884
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2003 JIM EGAN FIRE REVIEW Approved
11/05/2003 MELISSA POULIN WWM REVIEW Approved
11/18/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved TO0CM04884 DENIED 11/6/03
1. Per Shane Hevelone, one pump is new, and one pump is a replacement of an existing. Please clarify this on the plans.
2. Per Shane Hevelone, the existing pump to be replaced is on Panel LP, Circuit 13. Please clarify this on the plans. And if that is the case, please resolve the discrepancy between the protection and KVA rating of Circuit 13, and that of Circuit 38, which is dedicated to the new pump. Since the pumps are identical, conductor sizing, circuit breaker sizing, and KVA rating of circuits should be identical.
3. Please specify overload protection for the new pumps, per NEC 430 Part C, unless they are thermally protected, or unless their circuit breakers have been sized per the Manufacturer's recommendations.
4. Specify conductor size for pumps.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
11/06/2003 ANGIE SHOFFSTALL REJECT SHELF Completed