Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM04884
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/05/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
11/05/2003 | MELISSA POULIN | WWM | REVIEW | Approved | |
11/18/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TO0CM04884 DENIED 11/6/03 1. Per Shane Hevelone, one pump is new, and one pump is a replacement of an existing. Please clarify this on the plans. 2. Per Shane Hevelone, the existing pump to be replaced is on Panel LP, Circuit 13. Please clarify this on the plans. And if that is the case, please resolve the discrepancy between the protection and KVA rating of Circuit 13, and that of Circuit 38, which is dedicated to the new pump. Since the pumps are identical, conductor sizing, circuit breaker sizing, and KVA rating of circuits should be identical. 3. Please specify overload protection for the new pumps, per NEC 430 Part C, unless they are thermally protected, or unless their circuit breakers have been sized per the Manufacturer's recommendations. 4. Specify conductor size for pumps. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/14/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
11/06/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |