Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2003 JIM EGAN FIRE REVIEW Approved
11/05/2003 MELISSA POULIN WWM REVIEW Approved
11/18/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved TO0CM04884 DENIED 11/6/03
1. Per Shane Hevelone, one pump is new, and one pump is a replacement of an existing. Please clarify this on the plans.
2. Per Shane Hevelone, the existing pump to be replaced is on Panel LP, Circuit 13. Please clarify this on the plans. And if that is the case, please resolve the discrepancy between the protection and KVA rating of Circuit 13, and that of Circuit 38, which is dedicated to the new pump. Since the pumps are identical, conductor sizing, circuit breaker sizing, and KVA rating of circuits should be identical.
3. Please specify overload protection for the new pumps, per NEC 430 Part C, unless they are thermally protected, or unless their circuit breakers have been sized per the Manufacturer's recommendations.
4. Specify conductor size for pumps.