Permit Number: T03CM04884
Parcel: 133231610

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM04884
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/10/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts in drain lines from catch basins to sump basin in pit. Reference Section 707.5, UPC 1994.
2. Clarify pit layout including location of sink to be removed from pit.
3. Provide information regarding howt the perimeter drain is arranged and what is being drained (e.g. parking lot runoff).
Provide information to show that removal of the service sink will not effect the required minimum fixtures for the building. Reference Section 2900, IBC 2000.
11/04/2003 DROBEY1 ZONING REVIEW Needs Review
11/04/2003 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
11/04/2003 DROBEY1 ENGINEERING REVIEW Needs Review
11/04/2003 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review