Permit Number - T03CM04873
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/17/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 10/14/03 T03CM04873 Equipment Grounding conductor between wireway and disconnects for the new chillers shall be sized per NEC Table 250-122. Considering that the 400 A CB at the SES is the OC Device ahead of such equipment, minimum GEC size shall be #3. |