Permit Number: T03CM04873
Parcel: 12709001E

Address:
535 N WILMOT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM04873
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/17/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 10/14/03 T03CM04873
Equipment Grounding conductor between wireway and disconnects for the new chillers shall be sized per NEC Table 250-122. Considering that the 400 A CB at the SES is the OC Device ahead of such equipment, minimum GEC size shall be #3.