Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM04853
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | Zoning 1/02/2004 1) provide a copy of the approved site plan for the addition which has a zero setback along the north lot line. If there is not permit, additional comments will be necessary as will application for and approval of a Lot Development Option. |
| 12/31/2003 | David Witt | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T03CM04853 1/7/04 2315 N. MADELYN CIRCLE PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. PROVIDE FOOTINGS UNDER THE POSTS. ………..EXISTING? STRUCTURAL PLANS: 1. SPECIFY THE RIDGE BEAM. ELEVATIONS: 1. HOW ARE THE RAFTER BAYS VENTILATED? 2. PROVIDE SAFETY GLASS FOR THE WINDOW THAT IS LESS THAN 2ft. FROM THE DOOR. SECTIONS - DETAILS - MISC. NOTES: 1. PROVIDE, IN THE CROSS SECTION, THE MEMBER SIZES AND CONNECTIONS. PLUMBING PLANS: 1. THE WATER DISTRIBUTION SYSTEM IS SAID TO BE PIPED WITH "PEGS" ? PLEASE CLARIFY. DO YOU MEAN "PEX" ? 2. FROM WHERE DOES THE WATER COME? WATER METER? IF FROM ANOTHER WATER LINE, PLEASE JUSTIFY THAT LINES ADEQUACY. SEE U.P.C. SECTION 610.0 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/09/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 01/07/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |