Permit Number: T03CM04846
Parcel: 122160010

Address:
3645 E PIMA ST

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM04846
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2003 JIM EGAN FIRE REVIEW Approved
10/16/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. Dimensionally locate New Light Poles on site from two adjacent property lines.
S2. Submit Shop Drawings as noted for :
1. Light Poles
2. Luminare mounts/brackets.
S3. Provide Inspection Program conforming to requirements of 1997 Uniform Administrative Code Sec 302.5.
S4. Special Inspection as Noted for:
1. Caissons
2. Bolts in concrete
3. Field welding
4. Shop welding
5. Light poles 6. Installation of luminare mount/bracket
7. Luminare mounting
If you have questions regarding these comments, please call Douglas G Laakso, Structural Plans Examiner, at (520) 791-5550 x 1111.
10/27/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Provide load calculationsfor panel "ST"(sheet e-5). 2.Provide the available fault current and calculations.Both track and softball field.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
10/28/2003 ANGIE SHOFFSTALL REJECT SHELF Completed