Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM04846
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/16/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. Dimensionally locate New Light Poles on site from two adjacent property lines. S2. Submit Shop Drawings as noted for : 1. Light Poles 2. Luminare mounts/brackets. S3. Provide Inspection Program conforming to requirements of 1997 Uniform Administrative Code Sec 302.5. S4. Special Inspection as Noted for: 1. Caissons 2. Bolts in concrete 3. Field welding 4. Shop welding 5. Light poles 6. Installation of luminare mount/bracket 7. Luminare mounting If you have questions regarding these comments, please call Douglas G Laakso, Structural Plans Examiner, at (520) 791-5550 x 1111. |
| 10/27/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Provide load calculationsfor panel "ST"(sheet e-5). 2.Provide the available fault current and calculations.Both track and softball field. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/29/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 10/28/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |