Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM04827
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/22/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
10/22/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | STRUCTURAL COMMENTS General 1. Please clarify and provide seismic design analysis per IBC 1622.3.4 requirements. For Storage Racks supported above grade, the value of CS in the RMI Standard specification shall not be less than the value determined for Fp in accordance with IBC 1621.1.4 and with Rp taken as equal to R and ap taken as equal to 2.5. Recheck lateral resisting system in longitudinal and transverse direction of Storage Racks, and verify R factors in longitudinal and transverse direction for compliance with IBC Tables 1617.6 and 1622.2.5(1), where R shall not be less than 4. Please address lateral force resisting system that has been chosen for both directions and update Structural Calculations accordingly. 2. Recheck Foundation Calculations based on ACI 318-99, Section 22.5. When existing Storage Racks are supposed to be installed into existing slab, it shall be assumed as non-reinforced unless inspection testing is utilized. Please clarify. |
10/22/2003 | EROSE1 | WATER | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/22/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |