Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM04827
Parcel: 137055240

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM04827
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied STRUCTURAL COMMENTS
General
1. Please clarify and provide seismic design analysis per IBC 1622.3.4 requirements. For Storage Racks supported above grade, the value of CS in the RMI Standard specification shall not be less than the value determined for Fp in accordance with IBC 1621.1.4 and with Rp taken as equal to R and ap taken as equal to 2.5. Recheck lateral resisting system in longitudinal and transverse direction of Storage Racks, and verify R factors in longitudinal and transverse direction for compliance with IBC Tables 1617.6 and 1622.2.5(1), where R shall not be less than 4. Please address lateral force resisting system that has been chosen for both directions and update Structural Calculations accordingly.

2. Recheck Foundation Calculations based on ACI 318-99, Section 22.5. When existing Storage Racks are supposed to be installed into existing slab, it shall be assumed as non-reinforced unless inspection testing is utilized. Please clarify.
10/22/2003 EROSE1 WWM REVIEW Needs Review
10/22/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2003 ELAINE ROSE OUT TO CUSTOMER Completed