Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM04824
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2003 | LLESNY1 | WATER | REVIEW | Passed | |
| 11/03/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | SCOPE OF REVIEW: The scope of this review covers Plumbing, Mechanical and Electrical (the architectural and structural were checked by the City of Tucson). All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL: q There are no general comments to be addressed. MECHANICAL: q The outside air schedule on Sheet M2.0 lists all the mechanical units as serving "offices" with 20 c.f.m. per person. However, there is a reception area, exam rooms, and a conference room, none of which is reflected in the schedule. Please revise. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q There are no electrical comments to be addressed. -End of Review- |
| 11/03/2003 | EROSE1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/03/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |