| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2003 | Patricia Gehlen | ZONING | REVIEW | Denied | Zoning 10/28/2003 A copy of the last approved site plan is required prior to review. At this time, zoning comments may not be made until the last approved site plan is provided. |
| 11/03/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Occupancy classification for the proposed structure shall be an S-2. Reference section 311 IBC. Revise plans. 2. Parking canopy does not have the required amount of opening per section 406.3.3.1 IBC to be considered an unenclosed parking garage. Provide mechanical ventilation or create openings as allowed by Tables 602 & 704.8 IBC. |