Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-RESIDENTIAL
Permit Number - T03CM04808
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
| 11/19/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet G1.1 1. Please provide the sheet number of the title sheet to correspond with the drawing index. 2. Revise the text in general note 1 to indicate the City of Tucson as the governing jurisdiction. 3. Specify diameter of existing HCS. Ref. UPC Table 5. Sheet C1.1 1. A separate electrical service is shown on this sheet. A dwelling unit shall be supplied by only one service. Ref. E3501.2. Please revise. Sheet A.1 1. Specify the evaluation report number for the stucco system. 2. Clarify why a firewall partition type is shown. This does not appear to be a listed assembly. Provide the listing number and detail if a firewall is to be approved. 3. Show window type W-1 at the four locations with construction dimensions on the dimension plan. Show sill height dimensions for all windows. 4. Revise note 1 to indicate the IRC requirement. Ref. R307.2. Sheet A2.1 1. Specify roof vent size. Only 2 roof vents are shown. 7.71 square feet of net ventilation area is required. Ref. R806. Sheet A3.1 1. Coordinate key note references shown on the plan with the key notes identified in the legend. STRUCTURAL COMMENTS Sheet S1.0 1. Revise the nailing note to indicate the IRC requirements outlined in Tables R602.3. 2. Provide the truss design prepared by an Arizona P.E. Sheet S1.1 1. The footing schedule specifications do not correspond to detail 1/S1.2. Revise. Sheet S1.2 1. Coordinate footing details with the footing schedule. 2. Specify the minimum dimension for the new to existing joist lap. 3. Clarify why a firewall detail is provided. This does not appear to be a listed assembly. Provide the listing number and detail if a firewall is to be provided. PLUMBING COMMENTS Sheet MP1.1 1. Revise note 6 to indicate the 1994 UPC with State amendments as the governing code. The City of Tucson local amendments eliminate Chapters 25 through 32 of the IRC. 2. Revise note 7 to indicate that the minimum dimension above grade for the temperature pressure relief drain is 6". Ref. UPC 608.5. 3. Specify that showers and tub / shower combinations will have control valves of the pressure balance or thermostatic mixing valve type. Ref. UPC 410.7. 4. Show the existing fixture units for supply and waste line calculations. Ref. UPC Tables 6-3 and 7-3. MECHANICAL COMMENTS Sheet MP1.1 1. Please show the supply / drain lines for the evaporative cooler. 2. Specify provisions for temperature control in the bathrooms which are considered as habitable space. Ref. R303.6. 3. Note that the evaporative cooler is to be installed in accordance with M1413 and cross connection control will be provided as required by UPC 603. ELECTRICAL COMMENTS Sheet E1.1 1. Please address the requirement that a dwelling unit shall be supplied by only one service. Ref. E3501.2. 2. Specify a weatherproof ground fault circuit interrupter receptacle for the rooftop mechanical equipment. Ref. E3802.3. 3. Provide a separate means of disconnect for the rooftop evaporative cooler. ENERGY COMMENTS General 1. Provide the energy efficient data. Ref. N1102. |
| 11/19/2003 | EROSE1 | NPPO | REVIEW | Needs Review | |
| 11/19/2003 | EROSE1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/19/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |