Permit Number: T03CM04782
Parcel: 123070350

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM04782
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2003 Terry Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM04782
10/23/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. ZONING HAS DENIED THE SITE PLAN. SEE COMMENTS ON ACTIVITY CARD.

2. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING.

FOUNDATION PLANS:

1. NOTE AND DETAIL MINIMUM REINFORCING, OR PROVIDE CODE JUSTIFICATION OF ALTERNATE:
- STEMWALL - ONE (1) #4 REBAR IN THE BOTTOM OF THE FOOTING AND ONE (1) #4 REBAR IN THE TOP OF THE STEM

FLOOR PLANS:

1. WINDOWS WITHIN A 24" ARC OF EITHER VERTICAL EDGE OF A DOOR SHALL BE SAFETY GLASS. UBC SEC 2406.

2. PROVIDE ICBO # ON ALL SKYLIGHTS OVER 2' BY 4'.

STRUCTURAL PLANS:

1. PROVIDE STEEL LINTEL SIZES OR CALCS FOR MASONRY LINTELS OVER ALL WALL OPENINGS.

2. PROVIDE SPECIAL INSPECTION CERTIFICATE FOR EPOXY.

3. REMOVE FROM ALL DETAILS, ELEVATIONS AND FRAMING PLANS THE 4' OVER HANG AS DENIED BY ZONING

ELEVATIONS:

1. NOTE AND SIZE ALL ROOF DRAINS OR SCUPPERS ON FLAT-ROOFED AREAS PER R903.4.

2. SHOW CALCULATION OF ROOF VENTILATION IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

PLUMBING PLANS:

1. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

2. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

MECHANICAL PLANS:

1. CONDENSATE LINE NOT ALLOWED TO DUMP INTO TUB OVER FLOW.

ELECTRICAL PLANS:

1. SUBPANEL NOT ALLOWED IN A CLOTHES CLOSET.


2. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT THE FRONT OF THE DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3.

3. BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.

4. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

5. SHOW LOCATIONS OF SMOKE DETECTORS PER R317.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
10/29/2003 GERRY KOZIOL WWM REVIEW Denied Needs to show location/connection to public sewer. Needs WW credit evaluation for removal of 1 sink (if connected to sewer) if applicable. 8th fl 740-6500

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
10/29/2003 ANGIE SHOFFSTALL REJECT SHELF Completed