Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM04766
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2003 JIM TATE ENGINEERING REVIEW Approved
10/02/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
10/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/03/2003 JIM EGAN FIRE REVIEW Approved
10/03/2003 ROBERT SHERRY WATER REVIEW Approved
10/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/06/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
10/07/2003 MELISSA POULIN WWM REVIEW Approved
10/07/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 10/2/03
1. Show the location of the Panel DIG.
2. If lighting fixtures on Sheet E3.1 are on Panel DIG, show this in the schedule for that panel. Otherwise, document and clarify on the plans that lighting is fed from a different panel.
4. Add the following note to the plans: "All work in patient care areas shall be done in compliance with NEC 517-13."
3. Provide a disconnect for the WH per NEC 422-31 (b).

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2003 TAMI ACHONG OUT TO CUSTOMER Completed
10/07/2003 ANGIE SHOFFSTALL APPROVAL SHELF Completed