Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM04766
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/02/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 10/02/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/03/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/03/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/03/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/03/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/06/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/07/2003 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 10/07/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 10/2/03 1. Show the location of the Panel DIG. 2. If lighting fixtures on Sheet E3.1 are on Panel DIG, show this in the schedule for that panel. Otherwise, document and clarify on the plans that lighting is fed from a different panel. 4. Add the following note to the plans: "All work in patient care areas shall be done in compliance with NEC 517-13." 3. Provide a disconnect for the WH per NEC 422-31 (b). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/14/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 10/07/2003 | ANGIE SHOFFSTALL | APPROVAL SHELF | Completed |