10/02/2003 JIM EGAN FIRE REVIEW Approved
10/02/2003 DAN CASTRO ZONING REVIEW Approved
10/02/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
10/08/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/09/2003 GERRY KOZIOL WWM REVIEW Approved
10/15/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide independent indirect waste lines from the ice machine and the ice bin. Reference Section 803.0, UPC 1994.
2. Revise the water fixture units in the Fixture Connection Schedule (P2.0) to conform to Table 6.3, UPC 1994. Revise water pipe sizing as required. Reference Section 610.1, UPC 1994.
3. Provide sizes of the existing main water supply, landlord meter, and RPBP. Reference Section 103.2.3, UPC 1994.
4. Provide information to show that the addition of this project will not result in the main water supply being undersized for the total demand. Reference Section 103.2.3, UPC 1994.
5. Clarify the size of the new floor sink (FS).
6. Provide vent for grease trap. Reference Section 901.0, UPC 1994.
7. If the grease trap is equipped with an air relief by-pass, provide a vented trap for the 3-compartment sink. Reference Section 1011.5, UPC 1994.
8. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps will require backflow protection. Provide clarification of which pieces of equipment will require backflow protection and indicate the type of backflow protection device to be employed. Submit cut sheets for equipment having listed, integral backflow preventers or integral air gaps. Reference Section 603.0, UPC 1994.
10/17/2003 ROBERT SHERRY WATER REVIEW Approved
10/17/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied Provide justification for not providing a hood for the 50-hot dog warmer and flash steamer. Reference Sections 106.3.1 and 507.2, IMC 2000.
10/28/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved