Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A2
1. Specify garage framing holdowns at door openings.

Sheet A3
1. Specify safety glazing for window type 'C' within a 24" arc swing of door 5. Ref. R308.4.

2. Specify safety glazing for window type 'D', which has the bottom edge of the glazing less than 60" above the finished floor. Ref. R308.4.

3. Specify the smooth, hard, nonabsorbent surface to a height of 6' above the finished floor. Ref. R307.2.

4. Show attic accesses at garage and master suite as required by R807.

Sheet A4
1. Provide attic ventilation calculation and specify the size and location of venting. Ref. R806.

2. Please provide a detail with horizontal reinforcement specifications of the brick veneer construction at the new exterior walls. Ref. R703.7.

Sheet A6
1. Expand keynote 8, referenced in Detail 5/A6, to indicate wall finish to extend to a height of 6' above the finished floor. Ref. R307.2.

STRUCTURAL COMMENTS
Sheet A5
1. Please provide the structural design calculation for beam 'K' shown at the span adjacent to the pantry.

PLUMBING COMMENTS
Sheet P1
1. Show laundry room cleanouts. Ref. UPC 707.4.

2. Show ¾" gas down to the 75,000 BTUH water heater. Ref. UPC 1217.

MECHANICAL COMMENTS
Sheet M1
1. Keynote 25, for return air duct, was not found on the plan. Please clarify.

ELECTRICAL COMMENTS
Sheet E1
1. Specify lighting fixtures at the tub and shower as suitable for these locations. Ref. E3903.8.

ENERGY COMMENTS
General
1. Energy code calculations specify R-19 wall insulation. The construction details show both R-19 and R-13 wall insulation. Please clarify.