Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
02/02/2004 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
2/2/2004
Zoning may not review and approve building plans until the site plan is approved and included in the building plan submittal.
02/02/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the size, route, and termination of the condensate drain for AC-1.
02/02/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water sizing calculations using Table 6-4, UPC 1994. Include the information required in Section 610.7, UPC 1994. Table 6-4 includes a minimum residual pressure of 15 PSI but additional head losses (such as the water meter, reduced pressure backflow preventer, static lift (Section 610.7(3), UPC 1994), or additional residual pressure required by the specified fixtures) must be subtracted from the available water pressure to determine which of the 3 tables is to be used. Reference Section 610.4, UPC 1994.
2. Size the hot water piping per Sections 610.12 or 610.13, UPC 1994.
3. If natural gas not to be supplied to the building, remove the gas piping from Detail 4/PME.
02/03/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
03/02/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved 1.indicate disconnect at w.heater 2.provide conductor size for w.heater 3. provide individual circuit loads at panel schedule.