Permit Number: T03CM04671
Parcel: 106031160

Review Status: Completed

Review Details: SITE

Permit Number - T03CM04671
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2003 JIM EGAN FIRE REVIEW Approved
10/27/2003 Joseph Linville LANDSCAPE REVIEW Denied Include any landscape and screening information on the site plan required as a condition of approval for site plan # T03CM00078.
10/27/2003 PETER MCLAUGHLIN ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Poster Frost Assoc.
317 N. Court Ave
Tucson, Az 85701
(520) 882-6310

FROM: Peter McLaguhlin
Senior Planner
Development Services Dept.

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T03CM04671
La Paloma Family Services Neighborhood Rec Center
240 W. NavajoRoad
Site Plan Review (1st review)

TRANSMITTAL: October 27, 2003


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. This site plan is being reviewed as a less than 25% expansion of building area.
DS 2-02

2. Parking calculations on the last approved site plan are based on the old building (1260 square feet). Provide new parking calculations based on the size of the new building (1032 square feet).
DS 2-02.2.2.A.4
LUC 3.3.4

3. Add a legal description for the property to the site plan.
DS 2-02.2.1.A.2

4. Provide a calculation of percent building expansion or reduction detailing the existing and proposed square footages of buildings. Also, in addition to the lot coverage calculation given, provide a calculation of Floor Area Ratio (FAR) proposed and allowed.
DS 2-02.2.2.A.6
LUC 3.2.11
LUC 3.2.3.2

5. Show the location of existing class 2 bicycle parking as approved with permit #T03CM00078 in April, 2003.
DS 2-02.2.1.A.12

6. Dimension the street perimeter yard building setback proposed from the street property line.
DS 2-08.4.1

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


PMc\siteplans03\T03CM04671a
10/27/2003 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved
10/28/2003 JOE LINVILLE NPPO REVIEW Approved Exception per T03CM00078.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2003 DELMA ROBEY OUT TO CUSTOMER Completed
10/29/2003 ANGIE SHOFFSTALL REJECT SHELF Completed