Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM04660
Parcel: 110102780

Address:
3110 N SWAN RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM04660
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2003 EROSE1 WWM REVIEW Needs Review
10/28/2003 EROSE1 ENGINEERING REVIEW Needs Review
10/28/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A-1
1. Provide minimum plumbing fixtures or note on the plan that bottled water will be located in an accessible location and be on site at the time of final inspection. Ref. IBC Table 2902.1.

Sheet A-3
1. Please dimension the common use break counter at 34" maximum. Ref. ANSI A117.1, 903.

2. Please provide a maximum dimension of 18" from the side wall to the water closet centerline. Ref. ANSI A117.1, 604.2. Typical at all toilet rooms.

3. Please provide a minimum dimension of 54" from the rear wall to the end of the side wall grab bar. Ref ANSI A117.1, 604.5.1. Typical at all toilet rooms.

Sheet A-5
1. The masonry wall, shown as detail 7/A5, does not specify any provisions for horizontal reinforcement. Please revise this detail to include horizontal joint reinforcement at 16" on center. No bond beam is shown in the detail. Please clarify.

PLUMBING COMMENTS-The plumbing portion has been reviewed and approved.

MECHANICAL COMMENTS-The mechanical portion has been reviewed and approved.

ELECTRICAL COMMENTS
Sheet E-1
1. Please coordinate with energy comment 1.

ENERGY COMMENTS
General
1. Provide interior power lighting analysis. Ref. IECC Table 705.4.
10/28/2003 ELAINE ROSE ZONING REVIEW Needs Review
10/28/2003 EROSE1 WATER REVIEW Needs Review
10/28/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2003 ELAINE ROSE OUT TO CUSTOMER Completed