Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM04642
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/20/2003 | David Witt | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T03CM04642 10/21/03 4037 E. 17TH ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. SIMPSON LISTS THEIR PAHD42 @ OVER 1800# WITH AN END DISTANCE OF 8". R602.10.6 REQUIRES THESE HOLD-DOWNS TO BE ON END STUDS. HPAHD22? 2. TWO HOLD-DOWNS ARE REQUIRED TO BE PROVIDED FOR EACH BRACED WALL PANEL. PLEASE PROVIDE TWO HOLD-DOWNS FOR THE TWO NORTH/SOUTH BRACED WALL PANELS @ THE "NEW M. BATH". 3. THE FOOTING REFERS TO DETAILS ON SHEET A8. SHOULD THIS BE A6? 4. 1 / A6 & FRAMING NOTES / A7 ; THE ANCHOR BOLTS FOR ALTERNATE BRACED WALL PANELS (R602.10.6) ARE REQUIRED TO BE LOCATED AT QUARTER-POINTS. STRUCTURAL PLANS: 1. HEADER SCHEDULE / A7 ; WHY ARE TWO JACKS REQUIRED FOR ONE HEADER WHILE ONLY ONE JACK IS REQUIRED FOR LONGER HEADER SPANS? 2. FRAMING PLAN / A7 ; THE DETAILS ARE REFERRING TO SHEET A8. SHOULD THIS BE A7? 3. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. SECTIONS - DETAILS - MISC. NOTES: 1. 4 & 6 / A7 ; PLEASE SPECIFY SAG RESISTANT GYP. BOARD ON THE CEILING (TABLE R702.3.5 FOOTNOTE D) PLUMBING PLANS: 1. U.P.C. TABLE 6-4 REQUIRES A 1" WATER SERVICE LINE FOR 27 FIXTURE UNITS @ 100'. PLEASE JUSTIFY THE ¾" WATER SERVICE LINE. 2. THE NEW PLUMBING FIXTURE SCHEDULE LISTS 1 NEW LAVATORY BUT THE FLOOR PLAN SHOWS 2 NEW LAVATORIES. 3. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE APPLIANCE ON THE SYSTEM PER UPC 1217.2 4. THE NEW PLUMBING FIXTURE SCHEDULE LISTS TWO TUB/SHOWERS BUT THE FLOOR PLAN SHOWS ONLY ONE. MECHANICAL PLANS: 1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC. ELECTRICAL PLANS: 1. SUB-PANELS REQUIRE WORKING SPACE AS REQUIRED BY R3805.2. PLEASE RELOCATE THE SUB-PANEL IN THE WATER HEATER CLOSET, PROVIDE A CIRCUIT FROM THE MAIN PANEL, SIZE THE FEEDERS AND PROVIDE A SUB-PANEL SCHEDULE. 2. PLEASE NOTE LIGHT FIXTURES OVER THE BATHTUB ARE TO BE LISTED AS APPROVED FOR USE IN WET AREAS. 3. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED OUTLET BOXES SHALL BE USED, PER E4001.6. 4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11. 5. R317.1.1 REQUIRES EXISTING SLEEPING AREAS TO BE PROVIDED WITH SMOKE ALARMS. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 10/22/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |