Permit Number: T03CM04626
Parcel: 108192420

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM04626
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2003 EROSE1 WATER REVIEW Completed
10/14/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q The shower in the accessible restroom needs to be accessible as well [2000 IBC Sec. 1108.2]. If the shower was in the other restroom then it would be exempt [2000 IBC Sec. 1108.2 Exception 1].

STRUCTURAL:

q There are no structural comments to be addressed.

MECHANICAL:

q Please coordinate the outside air schedule on Sheet M2 with the plans. Some spaces are listed more than once (i.e. Reception, Large Office, Kitchen) while other spaces are not listed at all (i.e. Waiting, Conference, Break Room). It might also help if the room numbers were listed as the title in the schedule indicates.

q Check the quantities indicated for outside air relative to what is being provided. The total quantity of outside air per the Outside Air Schedule on Sheet M2 is 710 c.f.m (assuming that there are only 2 toilets - the schedule indicates 3). The equipment lists 600 c.f.m.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2003 ELAINE ROSE OUT TO CUSTOMER Completed