Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM04615
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/01/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
10/01/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet A0.0 1. In the code analysis block, please revise the code references to indicate the 1999 NEC and the 2000 IFC as the governing codes for this project. 2. Door 04 is not shown on the plan. Please clarify. 3. Door 015 is not shown in the door schedule please clarify. 4. Two doors identified as 014 are shown in the door schedule. Please revise door numbering as applicable. 5. Provide door numbering and door schedule information for the new emergency exit door. Ref. IBC 1003.3.8. Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 6. Please dimension the landing at the new exit door. Ref. IBC 1003.3.1.5. Sheet A2 1. Specify the maximum slope of 50% for the threshold detail shown at 9/A2. Ref. IBC 1003.3.1.6. Sheet M101 1. Please clarify if condensing unit #4 is new or existing. Sheet M201 1. Specify how the minimum outdoor ventilation air requirement is met. Ref. IMC 403.3. Sheet M401 1. The temperature and humidity note has a text error. It appears this note should state "in the form of …. STRUCTURAL COMMENTS Sheet A2 1. Please provide full height details of wall types specifying connections at top and bottom capable of resisting a 5 psf horizontal force. Ref. 1607.13. PLUMBING COMMENTS Sheet P.001 1. Show the ½" HW to sink DH in the fixture unit schedule. Sheet P101 1. Please coordinate fixture venting on the plan with the information shown in the fixture unit schedule. ELECTRICAL COMMENTS Sheet E101 1. Provide panel schedule information for Panel HIC. 2. Please show means of egress illumination for the new exit door with power from the electrical supply and emergency power. IBC 1003.2.11.2. ENERGY COMMENTS - The energy portion has been reviewed and approved. |
10/01/2003 | EROSE1 | WATER | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/01/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |