Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM04589
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2004 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Denied | 1. Provide water and waste fixture unit calculations. 2. The 2" W serving 2 floor sinks, 3 floor drains, a hand sink, and a lavatory, is undersized. 3. Provide water pressure calculations to show how the water piping was sized. 4. Provide an upper terminal cleanout for the most remote floor sink and for branches over 5'-0" from the main building drain. Provide a cleanout for the hand sink. 5. Provide a trap for the indirect waste from the prep sink. Reference Section 803.0, UPC 1994. 6. Show source of water supply. 7. Show the size of the branches to the appliances in the kitchen. 8. Show size of initial gas pipe at the meter. |
| 02/26/2004 | EGRANT1 | WWM | REVIEW | Needs Review |