10/02/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A2.0
1. Please show landings at exterior doors. Ref. R313.

2. Specify vertical members at column footings CF number 1 through number 4.

Sheet A3.0
1. Show column members coordinate with CF number 1 through number 4.

Sheet A4.0
1. Show handrail at the stairs.

2. Show the locations where one hour dwelling unit separation occurs. Provide the item number from IBC 719.1(2) or the listing number from an approved testing agency for the assembly.


3. Coordinate opening protective requirements at the dwelling unit separation conditions.

4. Specify protection of penetrations at the dwelling unit separation conditions.

5. Provide details for the site built fireplace. Ref. R1001.

6. Specify door types at the master bedroom and living room.

7. Safety glazing is required for the double french doors adjacent to bedroom 3.

Sheet A6.0
1. Specify the listing number for the stucco system weep screeds.

STRUCTURAL COMMENTS
Sheet A3.0
1. Coordinate horizontal framing with rooftop mechanical equipment load..

PLUMBING COMMENTS
Sheet P1
1. Show the required cleanouts. Ref. UPC 707.4.

2. Show the gas line sizes. Ref. UPC 1217.

3. Provide a fullway valve for the supply service. Ref. UPC 605.3.

4. Provide a pressure and temperature relief. Ref. UPC 608.

MECHANICAL COMMENTS
Sheet M1
1. Show path and termination of exhaust vents.

2. Show the size of the exhaust relief openings.

3. Show the path and termination of the dryer vent.

ELECTRICAL COMMENTS
Sheet E1
1. Show circuit information on plan

2. Show subpanel location.

3. Revise code reference for grounding and bonding. Ref. IECC 3508, 3509.



ENERGY COMMENTS - The energy portion has been reviewed and approved.