Permit Number: T03CM04567
Parcel: 10711279A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04567
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2004 JIM TATE ENGINEERING REVIEW Denied A copy of the stamped approved Site Plan must be included in the submittal.
09/09/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts on horizontal drainage pipe over than five feet from the building drain. Show the cleanouts on detail 2/P1.3. Reference Section 707.4, UPC 1994.
2. Detail 2/P1.3 shows only one 3" VTR for each building drain but Sheet P1.2 shows 20 vents through the roof for each building drain. Please coordinate the drawings. Note: the drain and vent configuration shown for fixture P2 in units 5 and 6 is physically impossible.
3. Keynote 2 on sheet P1.1 and keynote 2 on sheet P1.2 do not agree on the materials to be used for the water piping. Because the sizes of the water pipes shown on the drawing are based on using copper in the building and Schedule 40 PVC outside of the building, if the contractor elects to install PEX instead, pipe sizes specifically for PEX must be shown on the drawing. Reference Section 610.1, UPC 1994.
09/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/20/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) The 1-Hr wall detail shall specify 5/8" type X gyp board.
2) Per section 1107.5.4-R-2 units of 4 or more shall be of type B units and shall comply
To chapter 10 of ANSI regarding (door widths (B) reinforcement of the walls A)
where grab bars may be used. (C) Water closets shall be a max of 18" from the wall.
See chapter 10 for any required dimensions of fixtures or other PH bathroom require-
ments.

3/23/2004

1) The previous comments of 3/23/04 have not been addressed. Submit a response
sheet addressing all comments.

9/22/04
1) Per section 1107.5.4-R-2 units of 4 or more shall be of type B units and shall comply
To chapter 10 of ANSI regarding (door widths (B) reinforcement of the walls A)
where grab bars may be used. (C) Water closets shall be a max of 18" from the wall.
See chapter 10 for any required dimensions of fixtures or other PH bathroom requirements.

2) Provide details showing how these requirements are being complied. See chapter
10 of ANSI and comply to all type B dwelling units.
3) Refer to comment no. 1 regarding a 1 HR. FIRE RATED construction, what about detail 11/S1.3, that detail is indicated as a fire wall but does not comply.
10/01/2004 PETER MCLAUGHLIN ZONING REVIEW Denied Approved site plan required.