Permit Number: T03CM04567
Parcel: 10711279A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04567
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide overflow roof drains. Reference Section D1.1, UPC 1994.
2. Comment not addressed. Show how the water supply to the entire apartment building and to apartments 5 and 6 is able to conform to the requirements of NFPA 13R, Sections 6.5 and 6.6.
3. Comment not addressed. A single 1" water meter is not approved for this project; it results in an excessive pressure drop (over 20 PSI). Reference Section 610.2, UPC 1994.
4. Comment not addressed. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Section 704.4, IECC 1998.
5. Comment not addressed. Provide adequate space for removal of the water heaters. Reference Section 511.0, UPC 1994.
6. Comment not addressed. Provide cleanouts on horizontal drainage pipe over than five feet from the building drain and at all sinks. Reference Section 707.4, UPC 1994.
7. Comment not addressed. Provide an additional cleanout on drainage pipe with an aggregate horizontal change of direction exceeding 135 degrees. Reference Section 707.5, UPC 1994.
8. Comment not addressed. Coordinate Detail 1/P1.3 with the floor plan on sheet P1.1.
9. Comment not addressed. Revise the drawings to show the hot water connected to the left side of the fittings. Reference Section 601.2, UPC 1994.
10. Comment not addressed. Revise the size of the water piping to conform to the calculations shown on the drawing. Reference Section 610.1, UPC 1994.
02/26/2004 Patricia Gilbert ENGINEERING REVIEW Denied Site plan approval is required prior to building plan approval.
03/01/2004 JIM EGAN FIRE REVIEW Approv-Cond Residential fire sprinklers required for Apartment Units #5 and #6.
03/16/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied Comments from previous submittal were not addressed, typical.
03/23/2004 PETER MCLAUGHLIN ZONING REVIEW Denied Bldg plans cannot be approved prior to site plan approval.
03/23/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) The 1-Hr wall detail shall specify 5/8" type X gyp board.
2) Per section 1107.5.4-R-2 units of 4 or more shall be of type B units and shall comply
To chapter 10 of ANSI regarding (door widths (B) reinforcement of the walls A)
where grab bars may be used. (C) Water closets shall be a max of 18" from the wall.
See chapter 10 for any required dimensions of fixtures or other PH bathroom require-
ments.
3) Sliding glass doors to be tempered or safety glazing.
4) Provide smoke detectors as per Sect. 907.9.1.3.

3/23/2004

1) The previous comments of 3/23/04 have not been addressed. Submit a response
sheet addressing all comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/25/2004 TAMI ACHONG OUT TO CUSTOMER Completed
03/25/2004 SUE REEVES REJECT SHELF Completed