Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM04534
Parcel: 11615087J

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T03CM04534
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2003 JIM EGAN FIRE REVIEW Approv-Cond 1. Fire access roadways shall be minimum 20 feet in width.
2. Indicate helistop conforms to requirements of 2000 IFC Sec. 1107. Show on plan.
3. Provide complete fire sprinkler system design criteria on plan.
4. Fire sprinkler riser detail Sht. 15-9.3 is incorrect.
09/29/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Z_DO NOT USE
09/29/2003 PETER MCLAUGHLIN ZONING REVIEW Z_DO NOT USE
09/29/2003 PATRICIA GILBERT ENGINEERING REVIEW Z_DO NOT USE

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed