Permit Number: T03CM04530
Parcel: 124060180

Address:
840 E 7TH ST

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T03CM04530
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2003 EROSE1 WWM REVIEW Needs Review
12/04/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q The overhangs at the north and south ends of the new carport also need to be of 1-hour construction [2000 IRC Sec. R302.1]. Specifically the code requires 1-hour construction at the underside of the overhang within the 3'-0" fire separation distance.

STRUCTURAL:

q Detail 7 on Sheet A-2 implies that there is a bar of reinforcing running continuous in the footing but no size is provided. Please clarify.

PLUMBING:

q To where is the gas meter being relocated? The floor plan on Sheet A2 indicates that it is to be moved, however it does not show the new location.

ELECTRICAL:

q Provide a load calculation which includes the additional load on the exiting 200 amp panel.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2003 ELAINE ROSE OUT TO CUSTOMER Completed