Permit Number: T03CM04430
Parcel: 133369570

Address:
64 N HARRISON RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM04430
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A-2
1. Provide minimum fixture clearance in typical detail 1/A-2. Ref. ANSI A117.1, 604.3.1. Comment restated.

Sheet A-3
1. Provide a valuation report number for the sand finish stucco system referenced in keynote number 4. Comment restated. Response indicated was simply the word "RESPONSE:".

STRUCTURAL COMMENTS
GSN
1. Add to the list of Special Inspections earthwork, grading and filling and epoxy bolts as used.


Sheet S1
1. Provide masonry pier design due to out-of-plane wind loads by accounting for the adjacent openings plus combined with axial compression for the 12" thick piers at South wall. Ref. ACI 530-99/ASCE 5-99/ TMS 402-99 Section 2.3.3. Please see masonry piers P1 and undefined piers at front canopy with footing mark "F4". Provide cross section and reinforcement detailing of masonry piers at front canopy, not found addressed on plans.

PLUMBING COMMENTS
Sheet P-1
1. Show the hose bibbs referenced in the fixture schedule on the plan and provide cross connection control. Ref. UPC 603. Comment restated.

MECHANICAL COMMENTS
Sheet M-1
1. Provide outside ventilation air calculations. Ref. INC 403. The air conditioned space appears to be ready to lease. Comment restated.

ELECTRICAL COMMENTS
Sheet E-1
1. Provide fixture cut sheets for exterior lighting to determine compliance with outdoor lighting code requirements. Comment restated.

ENERGY COMMENTS
General
1. Include building envelope criteria for energy code compliance. Ref. IECC 701. Comment restated.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2003 ELAINE ROSE OUT TO CUSTOMER Completed