Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM04430
Parcel: 133369570

Address:
64 N HARRISON RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM04430
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2003 EROSE1 WWM REVIEW Needs Review
10/02/2003 ELAINE ROSE ZONING REVIEW Needs Review
10/02/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A-1
1. Provide landings at exterior doors with a minimum length measured in the direction of travel of 44". Ref/ IBC 1003.3.1.5.

2. Specify fire resistance of demising walls and item number from IBC 719.1 (2) or a listed assembly from an approved testing agency. See required separation of occupancies. Ref. IBC Table 302.3.3.

Sheet A-2
1. Provide minimum fixture clearance in typical detail 1/A-2. Ref. ANSI A117.1, 604.3.1.

2. Specify the minimum kick plate dimensions of 10". Ref. ANSI A117.1, 404.2.10.

Sheet A-2.1
1. In detail 6/A-2.1 specify maximum threshold slope of 50%. Ref. IBC 1003.3.1.6.

Sheet A-3
1. Typical partition wall detail 3/A-3 specifies 3 5/8" metal studs. Plan notes on Sheet A1 specify 5 5/8" metal studs. Please clarify.

2. Provide a valuation report number for the sand finish stucco system referenced in keynote number 4.

Sheet A-6
1. Specify point of termination for condensate drain. Ref. IMC 307.


STRUCTURAL COMMENTS
GSN
1. Update seismic data to reflect 2000IBC requirements. Ref. IBC 1603.1.5 to call out on plan seismic use group, SDS, SD1, Soil SiteCclass, Basic seismic force resisting system, design base shear and analysis procedure. Despite calculated values are conservative, see IBC 1615.1, 1615.1.2 for difference between mapped spectral accelerations SS and S1, and Designed spectral accelerations SDS and SD1.

2. Design of masonry by the Working Stress Design Method using one half of the allowable stresses to avoid the requirements is no longer permitted. Although the UBC permits half stress design of masonry for uninspected masonry construction, this is not consistent with the MSJC, which requires a minimum level of inspection for all masonry structures. IBC 1704.5 requires full allowable stress for masonry designed by the Working Stress Design Method along with mandatory inspection. Please revise.

3. Add to the list of Special Inspections the earthwork, grading and filling per Soils Report requirements, and field welding.

Sheet S1
1. Address column base plate of front TS4 x 4 x 1/4 columns, missing to be shown on plans. Also provide GLB beam to column connection.

2. Provide masonry pier design due to out-of-plane wind loads by accounting for the adjacent openings plus combined with axial compression. See 12" thick piers at South wall as well as 8" thick piers at West where 19' opening is applicable. Ref. ACI 530-99/ASCE 5-99/ TMS 402-99 Section 2.3.3.





Sheet SD-1
1. Provide ledger design in transverse direction addressing adequacy of 3" x 10" ledger w/ 7/8" @ 48"o.c. as shown on Detail 7. The submitted calculations on page 38-39 reflect only 4" x 12" ledger w/ 7/8" @16"o.c. Please clarify discrepancy.

2. Reference Details 3 & 4, revise/update lateral ties in masonry column/piers for conformance with ACI 530-99/ASCE 5-99/ TMS 402-99 Sections 2.1.4.6, and 2.1.5.2.

PLUMBING COMMENTS
Sheet P-1
1. Show the hose bibbs referenced in the fixture schedule on the plan and provide cross connection control. Ref. UPC 603.

MECHANICAL COMMENTS
General
1. Please clarify rooftop mechanical equipment is to be installed with the shell building.

Sheet M-1
1. Provide outside ventilation air calculations. Ref. INC 403.

ELECTRICAL COMMENTS
Sheet E-1
1. Provide fixture cut sheets for exterior lighting to determine compliance with outdoor lighting code requirements.

ENERGY COMMENTS
General
1. Include building envelope criteria for energy code compliance. Ref. IECC 701.
10/02/2003 EROSE1 WATER REVIEW Needs Review
10/02/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2003 ELAINE ROSE OUT TO CUSTOMER Completed