Permit Number: T03CM04423
Parcel: Unknown

Address:
7250 S TUCSON BL

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM04423
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet TUS-01A001
1. In the code summary notes, the application of sprayed fire-resistant materials is indicated to be a deferred submittal. Please clarify on the plan where this sprayed fire-resistant material is to be applied. Ref. IBC 1704.11.

STRUCTURAL COMMENTS
Sheet TUS01A200
1. Detail 1/A200 does not describe the manner in which the walls are to be connected to resist design forces. Please provide the structural detail that addresses this condition. Ref. IBC 1604.
10/02/2003 EROSE1 WWM REVIEW Needs Review
10/02/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2003 ELAINE ROSE OUT TO CUSTOMER Completed