Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM04422
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2003 EROSE1 WWM REVIEW Needs Review
09/25/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. The permit application did not include a valuation. Permit valuations shall include total value of work, including materials and labor, for which the permit is being issued, including plumbing, mechanical and electrical. Ref. IBC 108.3.

Sheet A1
1. Door 1, which does not show as a labeled door in the schedule, is located in a fire resistive wall per Sheet R3. Please clarify opening protective rating. Ref. IBC 714.2.



STRUCTURAL COMMENTS
General
1. Please coordinate with mechanical to verify adequacy of existing structural members and connections to be provided for the concentrated loads of the heat pumps and fan coils. Ref. IBC 1606.2.

PLUMBING COMMENTS
Sheet P1
1. Coordinate fixture unit call outs on the plan with those shown in the fixture schedule.

2. Specify water conservation fixture flow rates. Ref. UPC amendments.

3. The fixture unit values for supply and drainage are found in UPC Tables 6-3 and 7- 3. Please revise the fixture schedule per those tables.

MECHANICAL COMMENTS
Sheet M1
1. Provide specifications for the heat pumps and fan coils for inclusion with this permit or indicate that these units are by a separate permit. The plan note suggests they are to be included in the scope of work for this permit.

ELECTRICAL COMMENTS
Sheet E1
1. Circuits R-15, 17 and 19 for the Liebert equipment were not found. Please clarify.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
09/25/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2003 ELAINE ROSE OUT TO CUSTOMER Completed