Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM04419
Parcel: 119215930

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM04419
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2003 JIM EGAN FIRE REVIEW Approved
09/18/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Confirm that the existing vitrified clay pipe is listed for use under the building and that the proper separation is maintained between the VCP and the underground water piping. Reference Sections 313.4, 609.2, and 701.1, UPC 1994.
2. Provide calculations showing the water supply piping is sized in accordance with Section 610.4, UPC 1994. Include all existing fixtures when calculating the total demand and determining pipe sizes.
3. Revise the size of the wall cleanout at P2R/P2L to conform with Section 707.11, UPC 1994.
4. Revise specification item 16 to comply with Section 609.3.2, UPC 1994. Joints in underground copper piping are to be brazed not soldered.
09/18/2003 ROBERT SHERRY WATER REVIEW Approved
09/18/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/26/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
09/30/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied Refer to comments under "site" review comments - building plans may not be approved prior to site plan approval.
10/02/2003 GERRY KOZIOL WWM REVIEW Approved
10/02/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2003 DAVID RIVERA ZONING REVIEW Denied Building plans cannot be approved until a copy of the approved development is provided with the building plans and has been stamaped for site plan approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/16/2003 LISA LESNY OUT TO CUSTOMER Completed