Permit Number: T03CM04408
Parcel: 127120330

Address:
5602 E 5TH ST

Review Status: Completed

Review Details: REVISION

Permit Number - T03CM04408
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM04408 DENIED 8/11/04
1. Indicate Panel and circuit for porch lights. Ckt 2 on both indoor and outdoor panels do not apply as 2-pole ckts.
2. Provide cut sheets for new lighting fixtures.
3. Method of load calculation applies to dwelling units only. Add load calculations to panel schedules per NEC Article 220.
4. Specify conductor size and insulation type.
5. Specify conduit size and type.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2004 BETH GRANT OUT TO CUSTOMER Completed