Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM04408
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM04408 DENIED 8/11/04 1. Indicate Panel and circuit for porch lights. Ckt 2 on both indoor and outdoor panels do not apply as 2-pole ckts. 2. Provide cut sheets for new lighting fixtures. 3. Method of load calculation applies to dwelling units only. Add load calculations to panel schedules per NEC Article 220. 4. Specify conductor size and insulation type. 5. Specify conduit size and type. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/13/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |