Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/09/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
09/09/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water calculations to demonstrate that the piping has been sized in compliance with Section 610.1, UPC 1994. 2. Provide cleanout for P-2 located in Southeast restroom. Reference Section 707.4, UPC 1994. 3. Insulate HW piping. Reference Section 704.5, IECC 1998. |
09/09/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/09/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/09/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Modify required outside air flowrate for HP-2 to comform to requirements of Section 403.3.2, IMC 2000. |
09/18/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
09/18/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
09/22/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/22/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/22/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |