Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM04367
Parcel: 125043180

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T03CM04367
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2003 EROSE1 WWM REVIEW Needs Review
12/30/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 1
1. Structures are shown at or near the south and west property lines. A 3' distance is required from the property line or 1-hour fire resistive construction must be used. Ref. R302.

2. In the project data block, the occupancy groups of the residence are shown as R-1 and M-1. The correct occupancy group classifications are R-3 and U respectively. Please revise.

3. Show the water, sewer, gas and electric services and the points of connection on the site plan. Ref. R106.2.

Sheet A1
1. Specify any plumbing fixtures to be removed.


Sheet A2
1. Specify safety glazing for the windows within a 24" arc swing of doors 1 and 2. Ref. R308.4.5.

2. Provide construction details for the 5' and 6' walls. Dimension the linear distance of each type of wall.

3. Dimension ceiling heights. Ref. R305.

Sheet A3
1. Specify safety glazing for windows above tub / shower surfaces less than 60" above the walking surface. Ref. R308.4.4.

2. Specify safety glazing for the window adjacent to the stairs. Ref. R308.4.9.

STRUCTURAL COMMENTS
General
1. Provide two copies of the pre-engineered truss design sealed by an Arizona P.E. and reviewed by the structural engineer of record. The design must account for the concentrated loads imposed by the rooftop mechanical equipment.

PLUMBING COMMENTS
Sheet P1
1. Revise the fixture schedule code references to the UPC Tables 7-3 and 6-3.

2. Indicate BTUH demand of existing water heater. Ref. UPC 1217.

3. Revise water conservation code reference to indicate the UPC.

4. Show water supply with cross connection control for evaporative cooler.

5. Coordinate utility locations with the site plan.

MECHANICAL COMMENTS
Sheet M1
1. Specify exhaust fan provisions for the second floor bathroom.

2. Specify exhaust fan provisions for the range.

ELECTRICAL COMMENTS
Sheet E1
1. Specify listed fixtures for wet locations. Ref. R3903.8.

2. Specify GFCI for whirlpool bath. Ref. E4109.


3. Show the service diagram. Specify underground or overhead connection.

4. Please note that smoke alarms are required throughout the dwelling as required in new construction. Ref. R317.

ENERGY COMMENTS - The energy portion has been reviewed and approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/30/2003 ELAINE ROSE OUT TO CUSTOMER Completed