Permit Number: T03CM04350
Parcel: 117062070

Address:
127 S 5TH AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM04350
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2003 EROSE1 WWM REVIEW Needs Review
09/29/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A1.2
1. Provide the item number from IBC Table 719.1(2) or the listing number from an approved testing agency for the 1-hour rated partition shown in the wall legend.

2. The intent of general note 5 is unclear. Please clarify.

3. Please specify opening protective for door 147AA. Ref. IBC 714.2.

4. Please specify opening protective for window W1. Ref. IBC 714.3.

Sheet A4.1
1. Dimension the counter height for the common use break room at a maximum height of 34". Ref. ANSI A117.1, 902.3.

2. Dimension the bottom edge of the mirror at a maximum height of 40". Ref. ANSI A117.1, 604.4.

3. Dimension the height of the water closet seats at a maximum of 19". Ref. ANSI A117.1, 604.4.

Sheet A4.2.
1. The skylight curb detail appears to be mislabeled in 10/A4.2. It appears this should be 15/A5.1.

PLUMBING COMMENTS
Sheet P21
1. Specify low flow fixtures for new installation. Ref. UPC State amendments.

MECHANICAL COMMENTS - The mechanical portion has been reviewed and approved.

ELECTRICAL COMMENTS
Sheet E1.1
1. Provide the foundation design for the outdoor fixture "E".

2. Specify the grounding electrode conductor and bonding jumper for outdoor site pole lighting. Ref. NEC 250.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
09/29/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed