Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM04301
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/03/2003 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | S1. TWO TOILET ROOMS REQUIREDPER IBC SEC 29. ....... S2. CLARIFY ACCESSIBILITY PER IBC SEC 11 AND 34, AND ANSI A117.1-1998 ed. |
09/03/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show water pressure calculations and a fixture unit schedule for the project. Reference Section 610.1, UPC 1994. 2. Show required cleanouts on the waste riser diagram. Reference Section 707.4, UPC 1994. 3. A 2" trap arm is limited to 5 feet in length. |
09/03/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Denied on Walk-Through 9/3/03. |
09/03/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/03/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show exhaust fan for restroom. a minimum of 75 CFM is required per water closet. 2. Provide balancing data for hood, make-up air unit and outside air to existing AC unit. 3. Show ventilation calculations per Table 403.3, IMC 2000. |
09/04/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
09/04/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
09/09/2003 | CAGUILA1 | WWM | REVIEW | Needs Review | |
09/09/2003 | CAGUILA1 | FIRE | REVIEW | Needs Review |