Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM04301
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM04301
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2003 ANY BUILDING-COMMERCIAL REVIEW Denied S1. TWO TOILET ROOMS REQUIREDPER IBC SEC 29. ....... S2. CLARIFY ACCESSIBILITY PER IBC SEC 11 AND 34, AND ANSI A117.1-1998 ed.
09/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show water pressure calculations and a fixture unit schedule for the project. Reference Section 610.1, UPC 1994.
2. Show required cleanouts on the waste riser diagram. Reference Section 707.4, UPC 1994.
3. A 2" trap arm is limited to 5 feet in length.
09/03/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Denied on Walk-Through 9/3/03.
09/03/2003 ROBERT SHERRY WATER REVIEW Approved
09/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show exhaust fan for restroom. a minimum of 75 CFM is required per water closet.
2. Provide balancing data for hood, make-up air unit and outside air to existing AC unit.
3. Show ventilation calculations per Table 403.3, IMC 2000.
09/04/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
09/04/2003 DAN CASTRO ZONING REVIEW Approved
09/09/2003 CAGUILA1 WWM REVIEW Needs Review
09/09/2003 CAGUILA1 FIRE REVIEW Needs Review