Permit Number: T03CM04292
Parcel: 11918033B

Address:
3601 S 16TH AV

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T03CM04292
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2003 JIM EGAN FIRE REVIEW Denied 1. INDICATE MINIMUM GATE OPENING WIDTH OF 20 FEET ON PLAN.
2. INDICATE TYPE AND LOCATION OF EMERGENCY VEHICLE INGRESS DEVICES ON PLAN.
09/04/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved S1. PROVIDE FULLY READABLE COPIES OF SURVEY DRAWING. ........ ........................................................... S2. PROVIDE DETAILS FOR WALKTHROUGH SWING GATE/S . ......................................... . ....................... S3. PROVIDE OVERALL LINEAR FOOTAGE AND MAXIMUM HEIGHT FOR FENCE TO BE INSTALLED UNDER THIS PERMIT. .......................... .............................. S4. CLARIFY ACCESSIBILITY PER IBC SEC #11 & 34 AND ANSI A117.1-1998 ed. IMPROVE ACCESSIBILITY BY SPENDING 20% OF PROJECT COST ON ACCESSIBILITY.
09/11/2003 Loren Makus ENGINEERING REVIEW Approved
09/26/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied T03CM04292
1. Indicate location of TEP transformer on a scaled drawing.
2. Indicate location of new service pedestal on a scaled drawing.
3. Provide available fault current at new service pedestal.
4. Provide proper fault current rating at new service pedestal.

If you have any questions, call Linda Buczynski at 791-5550 x1106, or email at lbuczyn1@ ci.tucson.az.us.
10/01/2003 Patricia Gehlen ZONING REVIEW Denied Zoning
10/1/2003
A copy of the last approved site plan must be provided to ensure excess parking and PAAL width prior to approval. Required parking may not be used for other purposes.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2003 TAMI ACHONG OUT TO CUSTOMER Completed
10/01/2003 ANGIE SHOFFSTALL REJECT SHELF Completed