Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. HP-1, HP-2, and HP-3 are listed as 3-phase on Sheet M2.1, and the originally approved electrical drawings. They are 2-phase with this revision. Coordinate with Mechanical and clarify.
2. CKT B111-30 has a load on the power plan, but is a spare at the panel. Please clarify/correct.
3. B111-4 has 4 receptacles on power plan, but listed as only 540 VA on panel schedule. Shall read minimum of 720 VA.
4. Each of Circuits B111-22 and B111-24 have Equipment HH. On the panel schedule CKT 22 is listed as a general purpose receptacle with only 180 VA, but CKT has 1200 VA. If they serve the same equipment, they should have the same load. Please clarify.
5. CKT B115-17 has Equipment G, a Refrigerator, and another receptacle. Load should come to a minimum of 1044 VA, not 540.
6. B115-11 has 5 receptacles on power plan. Should be a minimum of 900 VA at panel, not 720.
7. B115-27 has receptacles on the power plan, and HVAC equipment on the Roof Power Plan and the Panel Schedule. Please clarify.
8. B111-1 has (10) Fixture A and (5) 2 X 4s. Load calc would exceed 1200 VA.
9. B111-3, with 7 Fixture B, would be 1050 VA. With the addition of the 2 X 4 load clac would be even higher. In any case, this figure would exceed 900 VA.
10. B111-5 has a sign and (3) Fixture B on the Lighting Plan. Load calc shold be at least 1650, not 450 VA.
11. Reflect the above changes in the Load Calculations.