Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM04234
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/02/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Include the exhaust from the existing inside restrooms in the outside air calculations. Reference Section 403.1, IMC 2000. 2. Recirculation of ventilation air from toilet rooms is prohibited; show that the balancing data for the existing restroom exhaust fans equals or exceeds the amount of air being supplied to the restrooms (minimum 75 cfm per water closet). Reference Table 403.3(b) IMC. 3. Utilize the net free area of the grilles and screens when calculating the required openings for the combustion and dilution air. Reference Section 709.1, IMC 2000, and Section 507.4, UPC 1994. 4. Show that the outside air intakes for the make-up air units and heat pumps are located at least 10 feet from exhaust discharges or plumbing vents. Reference Sections 401.5.1 and 506.3.13.3, IMC 2000. 5. Provide smoke detectors in the return air systems of all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC. |
09/02/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/02/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a schedule of water and waste fixture units for all plumbing fixtures and kitchen equipment using the values shown in Tables 6-3, 7-3, and A-3, UPC 1994. For kitchen equipment not listed in Tables 6-3 or A-3, use the size of their water connections and the values shown at the bottom of Table 6-3 to determine their fixture units. Include the total number of each fixture being installed. Revise pipe sizes as required. Reference Section 610.1, UPC 1994. 2. Show that the existing 1-1/2" water line is not overloaded with the addition of the new loads. Reference Section 302.3, Uniform Administrative Code 1997. 3. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Section 704.4, IECC 1998. 4. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994. 5. Provide cleanout for directly connected compartments of 3-compartment kitchen sink. Reference Section 707.4, UPC 1994. 6. Provide drains for reduced pressure backflow preventers. 7. Coordinate water and waste requirements of kitchen equipment with plumbing design and show connections on plans. Reference Section 302.3, Uniform Administrative Code 1997. 8. Use 24-hour operation for the grease interceptor calculation or justify using the reduced hours of operation. Reference Section H-4, UPC 1994. |
09/17/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/19/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Specify height of metal stud walls. Show how they are attached at top and bottom. If bracing is required at top, show detail. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/24/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
09/24/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |