Permit Number - T03CM04226
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2003 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Indicate all existing and proposed buildings and structures, including roof slope, downspouts, sidewalk scuppers and or splashguards. Drainage flowing across all pedestrian circulation paths shall be conveyed under the path for up to ten (10)-year frequency flood events. Indicate dimensioned details. D.S. 2-02.2.1.A.6

2. Indicate location, type, size and height of existing and proposed signage, if applicable. Include a dimensioned detail. D.S. 2-02.2.1.A.13

3. Indicate if sidewalks are existing or proposed.
10/13/2003 BLANCA ESPINO SANITATION REVIEW Denied 1. Refuse container location, size and access thereto fully dimensioned. D.S. 2-02.2.1.A.32 New projects including mobile home parks consisting of three (3) or more dwelling units will provide centralized on-site refuse storage, collection, and pickup areas with service access from within the tract or from an alley adjacent to the tract. D.S. 6-01.2.2 thru D.S 6-01.10.0. You may contact John Clark with Environmental Services at 791-3175 ext.1136 for approval of curbside pickup.
11/03/2003 Joseph Linville LANDSCAPE REVIEW Approved
11/03/2003 JOE LINVILLE NPPO REVIEW Approved Exception, 3 trees to be preserved.
11/04/2003 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Gus Chonis
1517 N. Wilmot Road #302
Tucson, AZ 85712
(520) 977-5970

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
T03CM04226
The Mirador Group, LLC
Catalina Terrace
1500 N. Catalina Avenue

TRANSMITTAL: November 5, 2003

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. If the concrete patio slabs (located adjacent to the buildings and extending into the perimeter yard building setback areas) are to be covered porches they must meet required perimeter bldg. setbacks (the greater of 10 feet or height of structure). Label them as "slab only" or "to remain uncovered". Otherwise, a Lot Development Option
DS 2-02.2.1.A.6
LUC 3.2.6.4

2. Label the centerline for Catalina Avenue along with the existing curb.
DS 2-02.2.1.A.19

3. Provide the development designator "K" for the proposed use.
LUC 2.3.5.2.A.2

4. Per LUC 2.3.6.1.A.4, the proposed residential use is subject to LUC 3.5.7.1.F. Please add a note which details these restrictions.
LUC 2.3.5.2.A.2

5. Add recordation information for the 10-foot wide TEP easement and the gas easement to the site plan.
DS 2-02.2.1.A.20

6. Add wheelstops to the four parking spaces to the west of the PAAL to prevent vehicles from overhanging landscaped areas. Dimension the wheelstops from the front of parking spaces. Wheelstops must be located two-and-one-half (2½) feet from the front of the parking spaces.
DS 3-05.2.3.C.2

7. If free-standing outdoor lighting is proposed for this site, please detail on the site plan.
DS 2-02.2.1.A.25

8. The location, type, size and height of any proposed free-standing signage must be shown.
DS 2-02.2.1.A.13

9. State the existing use of the property (i.e. vacant).
DS 2-02.2.1.A.31

10. Due to number of proposed units, bicycle parking must be provided. Add bicycle parking calcs to sheet 1. Bicycle parking must be shown fully dimensioned per DS 2-09 on sheet D.2.
LUC 3.3.4
DS 2-02.A.9
DS 2-09

11. Add to the parking space detail on sheet 10 the maximum slope of the handicap access ramps and aisles.
ANS/ IBC

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

PSMc: H:\PETER\Siteplans03\T00CM04226a
11/05/2003 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Denied See Zoning Review Comments
11/17/2003 LLESNY1 FIRE REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2003 LISA LESNY OUT TO CUSTOMER Completed