| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/03/2003 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Site plan must be approved. |
| 12/08/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide up and downstream manhole rim elevations. Reference Section 710.1, UPC 1994. 2. Comment not fully addressed. Provide water pipe sizing calculations. Include any hose bibbs, HVAC connections, or irrigation outlets in the calculations. Reference Section 610.1, UPC 1994. 3. Comment not addressed. Provide the size of the reduced pressure backflow preventer. Reference Section 610.2, UPC 1994. |
| 12/09/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/11/2003 | CRAIG GROSS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/11/2003 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |