Permit Number: T03CM04224
Parcel: 120082400

Address:
4626 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04224
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2003 LOREN MAKUS ENGINEERING REVIEW Denied Site plan must be approved.
12/08/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide up and downstream manhole rim elevations. Reference Section 710.1, UPC 1994.
2. Comment not fully addressed. Provide water pipe sizing calculations. Include any hose bibbs, HVAC connections, or irrigation outlets in the calculations. Reference Section 610.1, UPC 1994.
3. Comment not addressed. Provide the size of the reduced pressure backflow preventer. Reference Section 610.2, UPC 1994.
12/09/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
12/11/2003 CRAIG GROSS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed